EL3443 - Technical data
EL3443-00xx
Technical data | EL3443 | EL3443-0010 | EL3443-0011 | EL3443-0013 | EL3443-0020 | |
|---|---|---|---|---|---|---|
Number of inputs | 3 x current, 3 x voltage | |||||
Special feature | - | factory calibrated with calibration certificate | ||||
Technology | 3-phase power measurement | |||||
Oversampling factor | – | |||||
Internal sampling rate | approx. 9.7 kSps (per channel) | |||||
Sampling type | simultaneously across all channels | |||||
Ground reference | single ended | |||||
Distributed clocks | Optional (for determining the zero crossing time) | |||||
Update interval | one mains period (20 ms at 50 Hz) | |||||
Measured values | Current, voltage, active power, reactive power, apparent power, active energy, reactive energy, apparent energy, cos φ, frequency, THD, harmonics (up to 40th harmonic), power quality factor | |||||
Measuring voltage | max. 480 V AC 3~ (ULX-N: max. 277 V AC; max. 240 V DC) | |||||
Measuring current | max. 1 A (AC/DC), | max. 5 A (AC/DC), | max. 100 mA (AC/DC), | max. 333 mV (AC/DC), | max. 1 A (AC/DC), | |
Measuring error | 0.3% relative to the full scale value (U/I), | |||||
Measuring procedure | true RMS | |||||
Frequency range | 0 (direct current) and 12 … 400 Hz | |||||
Cut-off frequency | 3000 Hz | |||||
Electrical isolation | 2500 V | |||||
Update time | mains-synchronous | |||||
Current consumption Power contacts | – | |||||
Current consumption via E-bus | 120 mA typ. | |||||
Special features | Single-phase operation possible, mains monitoring functionality, precise voltage zero crossing determination | |||||
Weight | approx. 75 g | |||||
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) | |||||
on 35 mm mounting rail, conforms to EN 60715 | ||||||
Permissible ambient temperature range during operation | -25 °C ... +60 °C (extended temperature range) | 0 °C ... +55 °C | -25 °C ... +60 °C (extended temperature range) | |||
Permissible ambient temperature range during storage | -40 °C ... +85 °C | -25 °C ... +85 °C | -40 °C ... +85 °C | |||
Relative humidity | 95% no condensation | |||||
Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | |||||
EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 | |||||
Protection rating/installation position | IP20/any | |||||
Marking/Approval*) | CE, EAC, UKCA | |||||
*) Real applicable approvals/markings see type plate on the side (product marking).