Standard objects

Standard objects (0x1000-0x1FFF)

The standard objects have the same meaning for all EtherCAT slaves.

Index 1000 Device type

Index (hex)

Name

Meaning

Data type

Flags

Default

1000:0

Device type

Device type of the EtherCAT slave: The Lo-Word contains the CoE profile used (5001). The Hi-Word contains the module profile according to the modular device profile.

UINT32

RO

0x01561389 (22418313dec)

Index 1008 Device name

Index (hex)

Name

Meaning

Data type

Flags

Default

1008:0

Device name

Device name of the EtherCAT slave

STRING

RO

EL34xx

Index 1009 Hardware version

Index (hex)

Name

Meaning

Data type

Flags

Default

1009:0

Hardware version

Hardware version of the EtherCAT slave

STRING

RO

 

Index 100A Software Version

Index (hex)

Name

Meaning

Data type

Flags

Default

100A:0

Software version

Firmware version of the EtherCAT slave

STRING

RO

 

Index 100B Bootloader version

Index (hex)

Name

Meaning

Data type

Flags

Default

100B:0

Bootloader version

Bootloader version

STRING

RO

 

Index 1018 Identity

Index (hex)

Name

Meaning

Data type

Flags

Default

1018:0

Identity

Information for identifying the slave

UINT8

RO

0x04 (4dec)

1018:01

Vendor ID

Vendor ID of the EtherCAT slave

UINT32

RO

0x00000002 (2dec)

1018:02

Product code

Product code of the EtherCAT slave

UINT32

RO

0x0D743052 (225718354dec)

1018:03

Revision

Revision number of the EtherCAT slave; the Low Word (bit 0-15) indicates the special terminal number, the High Word (bit 16-31) refers to the device description

UINT32

RO

--

1018:04

Serial number

Serial number of the EtherCAT slave; the Low Byte (bit 0-7) of the Low Word contains the year of production, the High Byte (bit 8-15) of the Low Word contains the week of production, the High Word (bit 16-31) is 0

UINT32

RO

e.g. 0x00001E06 (week 30/2006)

Index 10E2 Manufacturer-specific Identification Code

Index (hex)

Name

Meaning

Data type

Flags

Default

10E2:0

Manufacturer-specific Identification Code

Manufacturer-specific Identification Code

UINT8

RO

0x01 (1dec)

10E2:01

SubIndex 001

reserved

STRING

RO

 

Index 10F0 Backup parameter

Index (hex)

Name

Meaning

Data type

Flags

Default

10F0:0

Backup parameter

Length of this object

UINT8

RO

0x01

10F0:01

Checksum

Checksum

UINT32

RW

0x00000000 (0dec)

Index 10F3 Diagnosis History

Index

Name

Meaning

Data type

Flags

Default

10F3:0

Diagnosis History

Maximum subindex

UINT8

RO

0x15 (21dec)

10F3:01

Maximum Messages

Maximum number of stored messages. A maximum of 50 messages can be stored

UINT8

RO

0x00 (0dec)

10F3:02

Newest Message

Subindex of the latest message

UINT8

RO

0x00 (0dec)

10F3:03

Newest Acknowledged Message

Subindex of the last confirmed message

UINT8

RW

0x00 (0dec)

10F3:04

New Messages Available

Indicates that a new message is available

BOOLEAN

RO

0x00 (0dec)

10F3:05

Flags

not used

UINT16

RW

0x0000 (0dec)

10F3:06

Diagnosis Message 001

Message 1

OCTET STRING[28]

RO

{0}

...

...

...

...

...

...

10F3:15

Diagnosis Message 016

Message 16

OCTET STRING[28]

RO

{0}

Index 10F8 Actual Time Stamp

Index

Name

Meaning

Data type

Flags

Default

10F8:0

Actual Time Stamp

Time stamp

UINT64

RO

0x0000000000000000 (0dec)

Index 10F9 Time Distribution Object

Index

Name

Meaning

Data type

Flags

Default

10F9:0

Time Distribution Object

Max Subindex

UINT8

RO

0x01 (1dec)

10F9:01

Distributed Time Value

Object for time distribution by the EtherCAT Master

INT64

RW

 

Index 1600 DPM RxPDO-Map Variant Value Out

Index (hex)

Name

Meaning

Data type

Flags

Default

1600:0

DPM RxPDO-Map Variant Value Out

PDO Mapping RxPDO

UINT8

RO

0x04 (4dec)

1600:01

SubIndex 001

1. PDO Mapping entry (object 0x7040 (DPM Variant Value Out), entry 0x11 (Index 1 REAL))

UINT32

RO

0x7040:11, 16

1600:02

SubIndex 002

2. PDO Mapping entry (object 0x7040 (DPM Variant Value Out), entry 0x12 (Index 2 REAL))

UINT32

RO

0x7040:12, 16

1600:03

SubIndex 003

3. PDO Mapping entry (object 0x7040 (DPM Variant Value Out), entry 0x13 (Index 3 REAL))

UINT32

RO

0x7040:13, 16

1600:04

SubIndex 004

4. PDO Mapping entry (object 0x7040 (DPM Variant Value Out), entry 0x14 (Index 4 ULINT))

UINT32

RO

0x7040:14, 16

Index 1601 DPM RxPDO-Map Data

Index (hex)

Name

Meaning

Data type

Flags

Default

1601:0

DPM RxPDO-Map Data

PDO Mapping RxPDO

UINT8

RO

0x14 (20dec)

1601:01

SubIndex 001

1. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x01 (Data 1))

UINT32

RO

0xF700:01, 32

1601:02

SubIndex 002

2. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x02 (Data 2))

UINT32

RO

0xF700:02, 32

1601:03

SubIndex 003

3. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x03 (Data 3))

UINT32

RO

0xF700:03, 32

1601:04

SubIndex 004

4. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x04 (Data 4))

UINT32

RO

0xF700:04, 32

1601:05

SubIndex 005

5. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x05 (Data 5))

UINT32

RO

0xF700:05, 32

1601:06

SubIndex 006

6. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x06 (Data 6))

UINT32

RO

0xF700:06, 32

1601:07

SubIndex 007

7. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x07 (Data 7))

UINT32

RO

0xF700:07, 32

1601:08

SubIndex 008

8. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x08 (Data 8))

UINT32

RO

0xF700:08, 32

1601:09

SubIndex 009

9. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x09 (Data 9))

UINT32

RO

0xF700:09, 32

1601:0A

SubIndex 010

10. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x0A (Data 10))

UINT32

RO

0xF700:0A, 32

1601:0B

SubIndex 011

11. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x0B (Data 11))

UINT32

RO

0xF700:0B, 32

1601:0C

SubIndex 012

12. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x0C (Data 12))

UINT32

RO

0xF700:0C, 32

1601:0D

SubIndex 013

13. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x0D (Data 13))

UINT32

RO

0xF700:0D, 32

1601:0E

SubIndex 014

14. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x0E (Data 14))

UINT32

RO

0xF700:0E, 32

1601:0F

SubIndex 015

15. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x0F (Data 15))

UINT32

RO

0xF700:0F, 32

1601:10

SubIndex 016

16. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x10 (Data 16))

UINT32

RO

0xF700:10, 32

1601:11

SubIndex 017

17. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x11 (Data 17))

UINT32

RO

0xF700:11, 32

1601:12

SubIndex 018

18. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x12 (Data 18))

UINT32

RO

0xF700:12, 32

1601:13

SubIndex 019

19. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x13 (Data 19))

UINT32

RO

0xF700:13, 32

1601:14

SubIndex 020

20. PDO Mapping entry (object 0xF700 (DPM Data), entry 0x14 (Data 20))

UINT32

RO

0xF700:14, 32

Index 1800 I1 TxPDO-Par Channel

Index (hex)

Name

Meaning

Data type

Flags

Default

1800:0

I1 TxPDO-Par Channel

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1800:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 1

OCTET-STRING[2]

RO

01 1A

Index 1801 I1 TxPDO-Par Current

Index (hex)

Name

Meaning

Data type

Flags

Default

1801:0

I1 TxPDO-Par Current

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1801:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 2

OCTET-STRING[2]

RO

00 1A

Index 1802 I2 TxPDO-Par Channel

Index (hex)

Name

Meaning

Data type

Flags

Default

1802:0

I2 TxPDO-Par Channel

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1802:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 3

OCTET-STRING[2]

RO

03 1A

Index 1803 I2 TxPDO-Par Current

Index (hex)

Name

Meaning

Data type

Flags

Default

1803:0

I2 TxPDO-Par Current

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1803:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 4

OCTET-STRING[2]

RO

02 1A

Index 1804 I3 TxPDO-Par Channel

Index (hex)

Name

Meaning

Data type

Flags

Default

1804:0

I3 TxPDO-Par Channel

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1804:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 5

OCTET-STRING[2]

RO

05 1A

Index 1805 I3 TxPDO-Par Current

Index (hex)

Name

Meaning

Data type

Flags

Default

1805:0

I3 TxPDO-Par Current

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1805:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 6

OCTET-STRING[2]

RO

04 1A

Index 1806 I4 TxPDO-Par Channel

Index (hex)

Name

Meaning

Data type

Flags

Default

1806:0

I4 TxPDO-Par Channel

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1806:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 7

OCTET-STRING[2]

RO

07 1A

Index 1807 I4 TxPDO-Par Current

Index (hex)

Name

Meaning

Data type

Flags

Default

1807:0

I4 TxPDO-Par Current

PDO parameter TxPDO

UINT8

RO

0x06 (6dec)

1807:06

Exclude TxPDOs

Specifies the TxPDOs (index of TxPDO mapping objects) that must not be transferred together with TxPDO 8

OCTET-STRING[2]

RO

06 1A

Index 1App I1-4 TxPDO-Map Channel

Index (hex)

Name

Meaning

Data type

Flags

Default

1App:0

TxPDO-Map Channel

PDO Mapping TxPDO

UINT8

RO

0x13 (19dec)

1App:01

SubIndex 001

1. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x01 (Overcurrent))

UINT32

RO

0x60nn:01, 1

1App:02

SubIndex 002

2. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x02 (Inaccurate Current))

UINT32

RO

0x60nn:02, 1

1App:03

SubIndex 003

3. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x03 (Current Guard Warning))

UINT32

RO

0x60nn:03, 1

1App:04

SubIndex 004

4. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x04 (Current Guard Error))

UINT32

RO

0x60nn:04, 1

1App:05

SubIndex 005

5. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x05 (Apparent Power Guard Warning))

UINT32

RO

0x60nn:05, 1

1App:06

SubIndex 006

6. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x06 (Apparent Power Guard Error))

UINT32

RO

0x60nn:06, 1

1App:07

SubIndex 007

7. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x07 (Active Power Guard Warning))

UINT32

RO

0x60nn:07, 1

1App:08

SubIndex 008

8. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x08 (Active Power Guard Error))

UINT32

RO

0x60nn:08, 1

1App:09

SubIndex 009

9. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x09 (Reactive Power Guard Warning))

UINT32

RO

0x60nn:09, 1

1App:0A

SubIndex 010

10. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x0A (Reactive Power Guard Error))

UINT32

RO

0x60nn:0A, 1

1App:0B

SubIndex 011

11. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x0B (DPM Inaccurate))

UINT32

RO

0x60nn:0B, 1

1App:0C

SubIndex 012

12. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x0C (DPM Timeout))

UINT32

RO

0x60nn:0C, 1

1App:0D

SubIndex 013

Reserved

UINT32

RO

0x0000:00, 3

1App:0E

SubIndex 014

14. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x60nn:10, 1

1App:0F

SubIndex 015

15. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x11 (Current))

UINT32

RO

0x60nn:11, 32

1App:10

SubIndex 016

16. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x12 (Active Power))

UINT32

RO

0x60nn:12, 32

1App:11

SubIndex 017

17. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x13 (Apparent Power))

UINT32

RO

0x60nn:13, 32

1App:12

SubIndex 018

18. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x14 (Reactive Power Fundamental))

UINT32

RO

0x60nn:14, 32

1App:13

SubIndex 019

19. PDO Mapping entry (object 0x60nn (DPM Channel), entry 0x15 (Active Energy))

UINT32

RO

0x60nn:15, 32

Assignment:

 

Channel

Variables

I1

I2

I3

I4

 

 

pp

00

02

04

06

 

 

nn

00

10

20

30

 

 

Index 1App I1-4 TxPDO-Map Current

Index (hex)

Name

Meaning

Data type

Flags

Default

1App:0

TxPDO-Map Current

PDO Mapping TxPDO

UINT8

RO

0x0A (10dec)

1App:01

SubIndex 001

reserved

UINT32

RO

0x0000:00, 2

1App:02

SubIndex 002

2. PDO Mapping entry (object 0x60nn (DPM Channel Current), entry 0x03 (Overcurrent))

UINT32

RO

0x60nn:03, 1

1App:03

SubIndex 003

reserved

UINT32

RO

0x0000:00, 1

1App:04

SubIndex 004

4. PDO Mapping entry (object 0x60nn (DPM Channel Current), entry 0x05 (Inaccurate Current))

UINT32

RO

0x60nn:05, 1

1App:05

SubIndex 005

reserved

UINT32

RO

0x0000:00, 2

1App:06

SubIndex 006

6. PDO Mapping entry (object 0x60nn (DPM Channel Current), entry 0x08 (Current Guard Warning))

UINT32

RO

0x60nn:08, 1

1App:07

SubIndex 007

7. PDO Mapping entry (object 0x60nn (DPM Channel Current), entry 0x09 (Current Guard Error))

UINT32

RO

0x60nn:09, 1

1App:08

SubIndex 008

reserved

UINT32

RO

0x0000:00, 6

1App:09

SubIndex 009

9. PDO Mapping entry (object 0x60nn (DPM Channel Current), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x60nn:10, 1

1App:0A

SubIndex 010

10. PDO Mapping entry (object 0x60nn (DPM Channel Current), entry 0x11 (Current))

UINT32

RO

0x60nn:11, 32

Assignment:

 

Channel

Variables

I1

I2

I3

I4

 

 

pp

01

03

05

07

 

 

nn

01

11

21

31

 

 

Index 1A0C DPM TxPDO-Map Variant Value In

Index (hex)

Name

Meaning

Data type

Flags

Default

1A0C:0

DPM TxPDO-Map Variant Value In

PDO Mapping TxPDO

UINT8

RO

0x0A (10dec)

1A0C:01

SubIndex 001

reserved

UINT32

RO

0x000:00, 15

1A0C:02

SubIndex 002

1. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x10 (TxPDO Toggle))

UINT32

RO

0x604A:10, 1

1A0C:03

SubIndex 003

2. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x11 (Index 1 REAL))

UINT32

RO

0x604A:11, 16

1A0C:04

SubIndex 004

3. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x12 (Value 1 REAL))

UINT32

RO

0x604A:12, 32

1A0C:05

SubIndex 005

4. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x13 (Index 2 REAL))

UINT32

RO

0x604A:13, 16

1A0C:06

SubIndex 006

5. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x14 (Value 2 REAL))

UINT32

RO

0x604A:14, 32

1A0C:07

SubIndex 007

6. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x15 (Index 3 REAL))

UINT32

RO

0x604A:15, 16

1A0C:08

SubIndex 008

7. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x16 (Value 3 REAL))

UINT32

RO

0x604A:16, 32

1A0C:09

SubIndex 009

8. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x17 (Index 4 ULINT))

UINT32

RO

0x604A:17, 16

1A0C:0A

SubIndex 010

9. PDO Mapping entry (object 0x604A (DPM Variant Value In), entry 0x18 (Value 4 ULINT))

UINT32

RO

0x604A:18, 64

Index 1C00 Sync manager type

Index (hex)

Name

Meaning

Data type

Flags

Default

1C00:0

Sync manager type

Length of this object

UINT8

RO

0x04 (4dec)

1C00:01

SubIndex 001

Sync-Manager Type Channel 1: Mailbox Write

UINT8

RW

0x01 (1dec)

1C00:02

SubIndex 002

Sync-Manager Type Channel 2: Mailbox Read

UINT8

RW

0x02 (2dec)

1C00:03

SubIndex 003

Sync-Manager Type Channel 3: Process Data Write (Outputs)

UINT8

RW

0x03 (3dec)

1C00:04

SubIndex 004

Sync-Manager Type Channel 4: Process Data Read (Inputs)

UINT8

RW

0x04 (4dec)

Index 1C12 RxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default

1C12:0

RxPDO assign

PDO Assign Outputs

UINT8

RW

0x02 (1dec)

1C12:01

SubIndex 001

1. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1600 (5632dec)

1C12:02

SubIndex 002

2. allocated RxPDO (contains the index of the associated RxPDO mapping object)

UINT16

RW

0x1601 (5633dec)

Index 1C13 TxPDO assign

Index (hex)

Name

Meaning

Data type

Flags

Default

1C13:0

TxPDO assign

PDO Assign Inputs

UINT8

RW

0x04 (4dec)

1C13:01

SubIndex 001

1. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A01 (6657dec)

1C13:02

SubIndex 002

2. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A03 (6659dec)

1C13:03

SubIndex 003

3. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A05 (6661dec)

1C13:04

SubIndex 004

4. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

0x1A07 (6663dec)

1C13:05

SubIndex 005

5. allocated TxPDO (contains the index of the associated TxPDO mapping object)

UINT16

RW

 

Index 1C32 SM output parameter

Index

Name

Meaning

Data type

Flags

Default

1C32:0

SM output parameter

Synchronization parameters for the outputs

UINT8

RO

0x20 (32dec)

1C32:01

Sync mode

Current synchronization mode:

0: Free Run

1: Synchron with SM 2 Event

2: DC-Mode - Synchron with SYNC0 Event

3: DC-Mode - Synchron with SYNC1 Event

UINT16

RW

0x0000 (0dec)

1C32:02

Cycle time

Cycle time (in ns):

Free Run: cycle time of the local timer

Synchron with SM 2 Event: cycle time of the master

DC-Mode: SYNC0/SYNC1 Cycle Time

UINT32

RW

0x0016E360 (1500000dec)

1C32:03

Shift time

Time between SYNC0 event and output of the outputs (in ns, DC mode only)

UINT32

RO

0x00000384 (900dec)

1C32:04

Sync modes supported

Sync modes supported:

Bit 0 = 1: Free Run is supported

Bit 1 = 1: Synchron with SM 2 Event is supported

Bit 2-3 = 01: DC-Mode is supported

Bit 4-5 = 10: Output Shift with SYNC1 Event (DC mode only)

Bit 14 = 1: dynamic times (measurement through writing of 1C32:08)

UINT16

RO

0x0805 (2053dec)

1C32:05

Minimum cycle time

Minimum cycle time (in ns)

UINT32

RO

0x0007A120 (500000dec)

1C32:06

Calc and copy time

Minimum time between SYNC0 and SYNC1 event (in ns, DC Mode only)

UINT32

RO

0x00000384 (900dec)

1C32:07

Minimum delay time

Minimum time between SYNC1 event and output of the outputs (in ns, DC mode only)

UINT32

RO

0x00000384 (900dec)

1C32:08

Command

0: Measurement of the local cycle time is stopped

1: Measurement of the local cycle time is started

The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09, 1C33:03, 1C33:06, 1C33:09 are updated with the maximum measured values.
For a subsequent measurement the measured values are reset

UINT16

RW

0x0000 (0dec)

1C32:09

Maximum delay time

Time between SYNC1 event and output of the outputs (in ns, DC mode only)

UINT32

RO

0x00000384 (900dec)

1C32:0B

SM event missed counter

Number of missed SM events in OPERATIONAL (DC Mode only)

UINT16

RO

0x0000 (0dec)

1C32:0C

Cycle exceeded counter

Number of occasions the cycle time was exceeded in OPERATIONAL (cycle was not completed in time or the next cycle began too early)

UINT16

RO

0x0000 (0dec)

1C32:0D

Shift too short counter

Number of intervals between SYNC0 and SYNC1 events that are too short (DC Mode only)

UINT16

RO

0x0000 (0dec)

Index 1C33 SM input parameter

Index (hex)

Name

Meaning

Data type

Flags

Default

1C33:0

SM input parameter

Synchronization parameters for the inputs

UINT8

RO

0x20 (32dec)

1C33:01

Sync mode

Current synchronization mode:

0: Free Run

1: Synchron with SM 3 Event (no outputs available)

2: DC - Synchron with SYNC0 Event

3: DC - Synchron with SYNC1 Event

34: Synchron with SM 2 Event (outputs available)

UINT16

RW

0x0000 (0dec)

1C33:02

Cycle time

as 1C32:02 

UINT32

RW

0x0016E360 (1500000dec)

1C33:03

Shift time

Time between SYNC0 event and reading of the inputs (in ns, DC Mode only)

UINT32

RO

0x00000384 (900dec)

1C33:04

Sync modes supported

Sync modes supported:

Bit 0: Free Run is supported

Bit 1: Synchron with SM 2 Event is supported (outputs available)

Bit 1: Synchron with SM 3 Event is supported (no outputs available)

Bit 2-3 = 01: DC-Mode is supported

Bit 4-5 = 01: Input shift through local event (outputs available)

Bit 4-5 = 10: Input shift with SYNC1 event (no outputs available)

Bit 14 = 1: dynamic times (measurement through writing of 1C32:08 or 1C33:08)

UINT16

RO

0x0805 (2053dec)

1C33:05

Minimum cycle time

as 1C32:05 

UINT32

RO

0x0007A120 (500000dec)

1C33:06

Calc and copy time

Time between reading of the inputs and the inputs being available for the master (in ns, DC Mode only)

UINT32

RO

0x0007A120 (500000dec)

1C33:07

Minimum delay time

Minimum time between SYNC1 event and output of the outputs (in ns, DC mode only)

UINT32

RO

0x00000384 (900dec)

1C33:08

Command

as 1C32:08

UINT16

RW

0x0000 (0dec)

1C33:09

Maximum delay time

Time between SYNC1 event and reading of the inputs (in ns, DC Mode only)

UINT32

RO

0x00000384 (900dec)

1C33:0B

SM event missed counter

as 1C32:11 

UINT16

RO

0x0000 (0dec)

1C33:0C

Cycle exceeded counter

as 1C32:12 

UINT16

RO

0x0000 (0dec)

1C33:0D

Shift too short counter

as 1C32:13 

UINT16

RO

0x0000 (0dec)

Index F000 Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

Largest subindex of this object

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index distance of the objects of the individual channels

UINT16

RW

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RW

0x0005 (5dec)

Index F008 Code word

Index (hex)

Name

Meaning

Data type

Flags

Default

F008:0

Code word

reserved

UINT32

RW

0x00000000 (0dec)

Standard objects 1:

Code Word

The vendor reserves the authority for the basic calibration of the terminals. The code word is therefore at present reserved.