Technical data
Technical data | EL3475 |
|---|---|
Number of inputs | 12 |
Wiring | 2-wire |
Oversampling factor | - |
Distributed clocks | optional (required for distributed power measurement) |
Update interval | RMS values 20 ms at 50 Hz and 100 ms for other values such as harmonics |
Measured values | current (with SVL or via DPM: voltage, active power, reactive power, apparent power, active energy, reactive energy, apparent energy, cos φ, frequency, THD, power quality factor, harmonics (up to the 50th harmonic)) |
Measuring voltage | via SVL |
Measuring current | via SCL |
Nominal voltage measurement range | 333 mV RMS |
Technical voltage measuring range | +/- 600 mV for 125 % overrange |
Maximum permissible time for voltages above +/- 460 mV | tmax < 10 s** |
Max. permitted overvoltage | +/- 1 V, above this voltage damage to the device cannot be ruled out |
Measuring error | current: 0.3 % (relative to full scale value) |
Update time | mains-synchronous |
Monitoring functions | undercurrents/overcurrents (adjustable) |
Electrical isolation | 2500 V (channel/bus) |
Current consumption via E-bus | typ. 150 mA |
Current consumption from the power contacts | - |
Special features | distributed power measurement (DPM), electronic nameplates can be read out |
Width in the process image | configurable |
Permissible ambient temperature range during operation | -25 °C ... +60 °C |
Permissible ambient temperature range during storage | -40 °C ... +85 °C |
Permissible relative air humidity | 95 %, no condensation |
Weight | approx. 75 g |
Dimensions (W x H x D) | approx. 24 mm x 100 mm x 52 mm |
Installation | on 35 mm DIN rail, conforms to EN 60715 |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection rating | IP20 |
Installation position | variable |
Approvals / markings* | CE, UKCA, EAC |
*) Real applicable approvals/markings see type plate on the side (product marking).
Notice | |
**) Consequences of prolonged operation above the nominal range of the measuring voltage Prolonged operation above the nominal range can lead to functional impairment and/or shortening of the service life. |