Configuration data

Index F800 PM Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

F800:0

PM Settings

 

Value

Description

UINT8

RO

0x26

F800:01

Low pass filter

Low pass filter

On

Filter enabled

BIT1

RW

0x01 (1dec)

F800:02

High pass filter

High pass filter

On

Filter enabled

BIT1

RW

0x01 (1dec)

F800:03

Measuring mode

Measuring method

0

3-wire connection delta, 4-wire connection star

BIT2

RW

0x00 (0dec)

1

reserved

2

reserved

F800:05

Frequence channel

Reference channel for frequency measurement

0

Phase L1

BIT2

RW

0x00 (0dec)

1

Phase L2

2

Phase L3

F800:0E

Cyclic accumulation

Reference channel for power/energy measurement

0

Phase L1

BIT2

RW

0x00 (0dec)

1

Phase L2

2

Phase L3

F800:21

Zero cross timeout

Zero crossing timeout

Unit: 1 period

UINT16

RW

0x0005 (5dec)

F800:22

Line cycle

Measuring cycle time

Unit: 1 period

UINT16

RW

0x000A (10dec)