EL3314-0002 - Configuration data (vendor-specific)

Index 80nF TC Vendor data Ch.(n+1) (for 0 ≤ n ≤ 3)

Index (hex)

Name

Meaning

Data type

Flags

Default

80nF:0

TC Vendor data

Maximum subindex

UINT8

RW

0x05 (5dec)

80nF:01

Calibration offset TC

Thermocouple offset (vendor calibration)

INT32

RW

0x00000000 (0dec)

80nF:02

Calibration gain TC

Thermocouple gain (vendor calibration)

UINT32

RW

0x00B43B00 (11811584dec)

80nF:03

Calibration offset 2,5 V

Offset 2.5 V-Measurement (vendor calibration)

INT32

RW

0x00000000 (0dec)

80nF:04

Calibration offset 2,5 V

Gain 2.5 V-Measurement (vendor calibration)

UINT32

RW

0xD0121300 (3490845440dec)

80nF:05

CJ Offset 1/256°C

Offset Coldjunction (vendor calibration)

INT32

RW

0x00000000 (0dec)