EL3314-0090 - Configuration data

Index 80n0 TC Settings (for Ch. 1 - 4 (0 ≤ n ≤ 3))

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:0

TC Settings

Max. Subindex

UINT8

RO

0x19 (25dec)

80n0:01

Enable user scale

User scaling is active.

BOOLEAN

RW

0x00 (0dec)

80n0:02

Presentation

0: Signed presentation, 0.1 °C/digit (default)

1: Absolute value with MSB as sign (signed amount representation), 0.1 °C/digit

2: High resolution, 0.01 °C/digit

BIT3

RW

0x00 (0dec)

80n0:05

Siemens bits

The S5 bits are shown in the three low-order bits as status display.

BOOLEAN

RW

0x00 (0dec)

80n0:06

Enable filter

This setting generally activates the basic filters in object 0x80n0:15. In the EL33xx these are technically realized in the ADC and can therefore not be switched off, even if they are set to "disabled" in the object.

BOOLEAN

RW

0x00 (0dec)

80n0:07

Enable limit 1

Limit 1 enabled

BOOLEAN

RW

0x00 (0dec)

80n0:08

Enable limit 2

Limit 2 enabled

BOOLEAN

RW

0x00 (0dec)

80n0:0A

Enable user calibration

Enabling of the user calibration

BOOLEAN

RW

0x00 (0dec)

80n0:0B

Enable vendor calibration

Enabling of the vendor calibration

BOOLEAN

RW

0x01 (1dec)

80n0:0C

Coldjunction compensation

0: internal (default)

1: no
Cold junction compensation is not active

2: Extern process data [1/10 °C]
Cold junction compensation takes place via the process data

BIT2

RW

0x00 (0dec)

80n0:0E

Disable wire break detection

0: Wire break detection is enabled
1: Wire break detection is disabled

BOOLEAN

RW

0x00 (0dec)

80n0:11

User scale offset

User scaling offset

Adjustable values: -32768…32767

INT16

RW

0x0000 (0dec)

80n0:12

User scale gain

Gain of the user scaling
The gain has a fixed-point representation with a factor of 2-16.
The value 65536 (0x00010000) corresponds to a gain value of 1.

Adjustable values: -2147483648…2147483647

INT32

RW

0x00010000 (65536dec)

80n0:13

Limit 1

First limit value for setting the status bits (resolution 0.1 °C)

Adjustable values: -32768…32767

INT16

RW

0x0000 (0dec)

80n0:14

Limit 2

Second limit value for setting the status bits (resolution 0.1 °C)

Adjustable values: -32768…32767

INT16

RW

0x0000 (0dec)

80n0:15

Filter settings

This object determines the basic digital filter settings.

UINT16

RW

0x0000 (0dec)

0: 50 Hz
1: 60 Hz
2: 100 Hz
3: 500 Hz
4: 1 kHz
5: 2 kHz
6: 3.75 kHz
7: 7.5 kHz
8: 15 kHz
9: 30 kHz
10: 5 Hz
11:10 Hz

Index (hex)

Name

Meaning

Data type

Flags

Default

80n0:17

User calibration offset

User calibration offset

INT16

RW

0x0000 (0dec)

80n0:18

User calibration gain

User calibration gain

UINT16

RW

0xFFFF (65535dec)

80n0:19

TC element

Thermocouple (Implemented temperature range) or measured variable

UINT16

RW

0x0000 (0dec)

0: Type: K -200 °C to 1370 °C
1: Type: J -100 °C to 1200 °C
2: Type: L 0 °C to 900 °C
3: Type: E -100 °C to 1000 °C
4: Type: T -200 °C to 400 °C
5: Type: N -100 °C to 1300 °C
6: Type: U 0 °C to 600 °C
7: Type: B 600 °C to 1800 °C
8: Type: R 0 °C to 1767 °C
9: Type: S 0 °C to 1760 °C
10: Type: C 0 °C to 2320 °C

100: ± 30 mV (1 µV resolution)
101: ± 60 mV (2 µV resolution)
102: ± 75 mV (4 µV resolution)

Index 8040 TSC Settings

Index (hex)

Name

Meaning

Data type

Flags

Default

8040:0

TSC Settings

Max. subindex

UINT8

RO

0x02 (2dec)

8040:01

Address

TwinSAFE SC Address

UINT16

RW

0x0000 (0dec)

8040:02

Connection Mode

Selection of TwinSAFE SC CRC

UINT32

RO

0x00000000 (0dec)