EL3314-0092 - output data

Index 70n0 TC Outputs Ch.(n+1) (for 0 ≤ n ≤ 3)

Index (hex)

Name

Meaning

Data type

Flags

Default

70n0:0

TC Outputs

Maximum subindex

UINT8

RO

0x11 (17dec)

70n0:11

CJCompensation

Temperature of the cold junction (resolution in 1/10°C)
(index 0x80n0:0C, comparison via the process data)

INT16

RO

0x0000 (0dec)

Index 7040 TSC Master Frame Elements

Index (hex)

Name

Meaning

Data type

Flags

Default

7040:0

TSC Master Frame Elements

Max. subindex

UINT8

RO

0x03 (3dec)

7040:01

TSC__Master Cmd

reserved

UINT8

RO

0x00 (0dec)

7040:02

TSC__Master ConnID

reserved

UINT16

RO

0x0000 (0dec)

7040:03

TSC__Master CRC_0

reserved

UINT16

RO