B-parameter equation (0x80n00:19, entry 0x111)
The B-parameter equation can be used for NTC sensors (thermistors), i.e. RTD elements with negative coefficient k.
Here the coefficient RT0 indicates the resistance at the temperature T0, the B-parameter can be taken from the information provided by the sensor manufacturer, or it can be determined by measuring the resistance at two known temperatures.
The following sample file (Download: ZIP) can be used to calculate the B-parameter. Enter the calculated parameters in the CoE directory 0x8002.
Fig.173: Table for calculating the B-parameter