Status word

The status information for each channel of the EL32xx and EL33xx is transmitted cyclically from the terminal to the EtherCAT Master as process data (PDO). Two versions of the device description are available for the EL32xx and EL33xx, representing the process image in individual and extended forms.

The difference can be seen in the revision number EL3xxx-xxxx-XXXX.

The EL32xx or EL33xx transmit the following process data:

The limit evaluation is set in the "8000" objects in the CoE directory.

Status word 1:

Differences in the versions of the EL32xx and EL33xx series

The revision differences are illustrated below, using the EL32xx series as an example. The principles of the description apply equally to the EL33xx series.

Revision -0016 (EL32xx-xxxx-0016)

These terminal revisions have the single process image, see “EL32xx-0000-0016 process image in the TwinCAT 2.11 representation”.
Each item of status information is transmitted as a single, linkable process data.

Status word 2:
Fig.50: EL32xx-0000-0016 process image in the TwinCAT 2.11 representation

Revisions -0017 (EL32xx-xxxx-0017) and higher

These terminal revisions also have the summarized process image, see “EL32xx-0000-0017 process image in the TwinCAT 2.11 representation”.
The individual units of information are assembled here in the usual Beckhoff representation as a 16-bit status word, and can be linked into the controller in this way.

Status word

Bit

SW.15

SW.14

SW.13

SW.12

SW.11

SW.10

SW.9

SW.8

SW.7

SW.6

SW.5

SW.4

SW.3

SW.2

SW.1

SW.0

Name

TxPDO Toggle

TxPDO State

-

-

-

-

-

-

-

Error

Limit 2

Limit 1

Overrange

Underrange

In addition to this, the consolidated "status" can be folded out through the "+" symbol, and the items of process data linked individually.

Status word 3:
Fig.51: EL32xx-0000-0017 process image in the TwinCAT 2.11 representation

The individual items of information can also be displayed in the overview window (A) on the right. By clicking on the button
Status word 4:
in the menu bar the information can also be displayed there.

Status word 5:
Fig.52: Consolidated process image in the extended representation under TwinCAT 2.11

Notes

Status word 7:
Fig.54: Typical result after scanning an EtherCAT system

Explanation about fig. “Typical result after scanning an EtherCAT system”: According to the overview on the right, an EL3201-0000-0016 was found in the configuration (*.tsm file), whereas the overview on the left shows revision -0017. The general downward compatibility of the EL terminals ensures that this kind of application is possible.