Pin assignment, display and diagnosis

EL3201

Pin assignment, display and diagnosis 1:
EL3201 pin assignment
Pin assignment, display and diagnosis 2:

Two-wire connection EL3201

If the EL3201 is operated with a two-wire connection, the inputs +R and +RL must be bridged by the user.

EL3201 – pin assignment

Terminal point

No.

Comment

+R1

1

Input +R1, current-carrying

+RL1

2

Input +RL1, de-energized sense line

-R1

3

Input -R1, current-carrying

-RL1

4

Input -RL1, de-energized sense line

n. c.

5

not used

n. c.

6

not used

-R1

7

Input -R1, current-carrying

Shield

8

Shield

Pin assignment, display and diagnosis 3:

Connection of analog RTD signal lines

To ensure that the analog signals can be measured with as little interference as possible, also observe the notes in the chapter "Connection of analog RTD signal lines".

EL3201 - LEDs

LED

Color

Meaning

RUN

green

This LED indicates the terminal's operating state:

off

State of the EtherCAT state machine: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates of the terminal

flashing

State of the EtherCAT state machine: PREOP = function for mailbox communication and different standard-settings set

Single flash

State of the EtherCAT state machine: SAFEOP = verification of the sync manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT state machine: OP = normal operating state; mailbox and process data communication is possible

ERROR1

red

Short circuit or wire breakage. The resistance is in the invalid range of the characteristic curve