Further application notes

Further application notes 1:

"Filter enable" setting

The filter function is always active, even if the object 0x8000:06 "Filter enable" is set to FALSE

Further application notes 2:

"Connection technology" setting

In addition to 2-, 3- and 4-wire connection (on the EL3204-0162, the 3- and 4-wire settings have no function), "not connected" can also be selected here for each channel. The channel concerned is completely disabled and the conversion time of the EL3204-0162 is correspondingly shortened.
By means of a double click on the corresponding object 0x80x0:1A, the respective channels can be switched off in the Set Value Dialog by selecting the "Enum" value "not connected". (See fig. "not connected" setting)

Further application notes 3:Fig.137: “not connected” setting