EL3162 - Technical data

Technical data

EL3162

analog inputs

2

Signal voltage

0 ...+10 V

Internal resistance

> 200 kΩ

Resolution

16 bit (including sign)

Sampling type

simultaneous

Ground reference

single-ended

Conversion time (default setting: 50 Hz filter)

approx. 50 µs

Input filter limit frequency

5 kHz

Measuring error (full measuring range)

< ±0.3 % (relative to full scale value)

Supply voltage for electronic

via the E-bus

Current consumption via E-bus

typ. 170 mA

Distributed Clocks

yes (from rev. EL316x-0000-0017)

Distributed Clocks precision

<< 1 µs

Support NoCoEStorage

yes

Electrical isolation

500 V (E-bus/field voltage)

Dielectric strength

max. 30 V

Bit width of the process image (default setting)

Inputs: 2 x 16 bit;
Status: 2 x 8 bit

Configuration

no address or configuration settings required

Weight

approx. 60 g

Permissible ambient temperature range during operation

0°C ... +55°C

Permissible ambient temperature range during storage

-25°C ... +85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Enhanced mechanical load capacity

yes, see also Installation instructions for enhanced mechanical load capacity

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, EAC, UKCA, CCC
ATEX, IECEx, cULus

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex nA IIC T4 Gc

IECEx

Ex nA IIC T4 Gc