Presentation, index 0x80n0:02
The measured value output is set in factory to two's complement representation (signed integer).
index 0x80n0:02 offers the possibility to change the method of representation of the measured value.
Signed integer representation
The negative output value is represented in two’s complement (negated + 1).
Measuring range 4…20 mA (NAMUR)
4…20 mA |
Decimal |
Hexadecimal |
---|---|---|
- |
32767 |
0x7FFF |
21 mA |
32425 |
0x7EAC |
20.5 mA |
31472 |
0x7A20 |
20 mA |
30518 |
0x7736 |
4 mA |
0 |
0x0000 |
3.8 mA |
-381 |
0xFE83 |
3.6 mA |
-763 |
0xFD05 |
- |
-32768 |
0x8000 |
Maximum representation range for 16 bit = -763dec .. +32425dec
![Presentation, index 0x80n0:02 1:](Images/png/3249384715__Web.png)
Measuring range 0…20 mA
0…20 mA |
Decimal |
Hexadecimal |
---|---|---|
0 mA |
0 |
0 |
20 mA |
30518 |
0x7736 |
21.474 mA |
32767 |
0x7FFF |
0…20 mA |
Decimal |
Hexadecimal |
---|---|---|
0 mA |
0 |
0 |
20 mA |
32767 |
0x7FFF |
Maximum representation range for 16 bit = 0dec .. +32767dec
![Presentation, index 0x80n0:02 2:](Images/png/17675418635__Web.png)
Measuring range 4…20 mA
4…20 mA |
Decimal |
Hexadecimal |
---|---|---|
0 mA |
-7629 |
0xE233 |
3.8 mA |
-381 |
0xFE83 |
4 mA |
0 |
0 |
20 mA |
30518 |
0x7736 |
21.474 mA |
32767 |
0x7FFF |
4…20 mA |
Decimal |
Hexadecimal |
---|---|---|
0 mA |
0 |
0 |
20 mA |
32767 |
0x7FFF |
Maximum representation range for 16 bit = -7629dec .. +32767dec
![Presentation, index 0x80n0:02 3:](Images/png/17675417355__Web.png)