Technical data

Technical data

EL3182

Number of inputs

2

Technology

HART Version 7

Signal type

single-ended

Signal current

0/4…20 mA

Power supply

via the E-bus

Internal resistance

typ. 250 Ω

Input filter limit frequency

25 Hz

Dielectric strength

max. 30 V

Measuring range, technical

generally 107 % of the nominal measuring range

Resolution

16 bit (incl. sign)

Sampling type

multiplex

Ground reference

single ended

Measuring error

< ±0.3 % (relative to full scale value)

Distributed clocks

Yes

Electrical isolation

500 V (E-bus/signal voltage)

Current consumption power contacts

-

Current consumption E-bus

typ. 130 mA

Bit width in the process image

8 byte, HART: 28 byte per channel as option

Special features

  • Standard and compact process image
  • Activatable FIR/IIR filters
  • Limit value monitoring
  • ExtendedRange 107 %
  • NE43 NAMUR

Max. allowed output current (Uv1 / Uv2)

typ. 150 mA (per connector)

Weight

approx. 60 g

Permissible ambient temperature range during operation

-25°C ... + 60°C

Permissible ambient temperature range during storage

-40°C ... + 85°C

Relative humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

according to EN 60068-2-6/EN 60068-2-27,
see also installation instructions for terminals with increased mechanical load capacity

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, CCC, UKCA, EAC
cULus, ATEX, IECEx, cFMus

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex nA IIC T4 Gc
II 3 D Ex tc IIIC T135 °C Dc

IECEx

Ex nA IIC T4 Gc
Ex tc IIIC T135 °C Dc

cFMus

Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc