EL3078 – Technical data

Analog inputs

EL3078

Number of inputs

8

Connection technology

2-wire

Ground reference

U, I single-ended

Resolution

16 bits (including sign)

Minimum EtherCAT cycle time

500 µs

Sampling type

Multiplex, approx. 60 µs delay between channels

Sampling time

1 ms

Rise time

3 ms typ. (0…90 %)

Internal resistance

  • Voltage measurement: > 200 kΩ
  • Current measurement: 100 Ω typ.

Input filter cut-off frequency

1.2 kHz

Overcurrent protection, nominal

typ. < 50 mA

Measuring error (total measuring range)

< ±0.3 % (related to the nominal full scale value)

Electrical isolation channel/channel

no

Voltage measurement

EL3078

Signal voltage

-10/0…+10 V

Voltage measuring range, nominal

-10/0…+10 V

Voltage measuring range, technical

-10.73…+10.73 V

Recommended operating voltage range
(against reference ground to GND/ 0 V power contact)

30 V

Destruction limit
(against reference ground to GND/ 0 V power contact)

30 V

Current measurement

EL3078

Signal current

-20/0/+4…+20 mA

Current measuring range, nominal

-20/0/+4…+20 mA

Current measuring range, technical

-21.47…+21.47 mA

Recommended operating voltage range
(against reference ground to GND/ 0 V power contact)

30 V

Destruction limit
(against reference ground to GND/ 0 V power contact)

30 V

Supply and potentials

EL3078

Power supply for the electronics

via the E-bus

Current consumption via E-bus

typ. 90 mA

Electrical isolation

Channel/E-bus: functional separation 707 V DC type test

Function and communication

EL3078

Support NoCoEStorage

yes

Configuration

no address or configuration settings required

Width in the process image

Inputs: 16 bytes

Distributed clocks

no

Special features

  • U/I parameterizable,
  • Extended Range 107 % pre-set,
  • Standard and compact process image,
  • Activatable FIR/IIR filters

Environmental conditions

EL3078

Permissible ambient temperature range during operation

0…+55 °C

Permissible ambient temperature range during storage

-25…+85 °C

Permissible relative air humidity

95 %, no condensation

General data

EL3078

Design

HD (High Density) housing with signal LED

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Weight

approx. 65 g

Installation

on 35 mm mounting rail, conforms to EN 60715

Installation position

variable

Standards and approvals

EL3078

Protection rating

IP20

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Approval / marking*)

CE, EAC, UKCA

*) Real applicable approvals/markings see type plate on the side (product marking).