EtherCAT master error messages
EtherCAT error messages specifically for the EL30xx are
|
Number |
Name |
Explanation |
|---|---|---|
|
0x06090031 |
ABORT_VALUE_TOO_GREAT |
CoE 0x8000:12 (user scale gain greater than 0x0007FFFF) |
|
0x06090032 |
ABORT_VALUE_TOO_SMALL |
CoE 0x8000:12 (user scale gain smaller than -0x0007FFFF) |
|
0x08000021 |
ABORT_DATA_CANNOT_BE_READ_OR_STORED_BECAUSE_OF_LOCAL_CONTROL |
CoE 0x80nF:0x no authorization to write manufacturer data CoE 0x1C33: Contents locked because filter active |
The Beckhoff TwinCAT EtherCAT master outputs the slave error message according to the ETG specification in plain text in the logger window:
Fig.233: TwinCAT logger window, example of incorrect StartUp entry under TwinCAT 2.11