Limit, Swap limit

Limit 1 (index 0x80n0:13) and Limit 2 (index 0x80n0:14)

Limit, Swap limit 1:

Limit evaluation

The limit evaluation assumes a signed representation. The conversion to the desired representation (index 0x80n0:02) only takes place after the limit evaluation.

Swap Limit (index 0x80n0:0E)

The limit function can be inverted by SwapLimitBits in index 0x80n0:0E.

Setting SwapLimitBits
in index 0x80n0:0E

Output value (2 bits)
in index 0x60n0:03 for limit 1
in index 0x60n0:05 for limit 2

FALSE (default setting)

  • 0: not active
  • 1: Value < limit value
  • 2: Value > limit value
  • 3: Value = limit value

TRUE

  • 0: not active
  • 1: Value > limit value
  • 2: Value < limit value
  • 3: Value = limit value

The Swap limit function („Swap limit bits“, CoE object 0x80n0:0E) is available according to the table below

Terminal

Swap limit function from

EL300x

Firmware 05, Rev. EL300x-000-0018

EL301x,
EL302x

Firmware 01, Rev. EL301x-0000-0016
Firmware 01, Rev. EL302x-0000-0016

EL3041,
EL3042, EL3042-0017

Firmware 05, Rev. EL3041-0000-0017
Firmware 05, Rev. EL3042-xxxx-0017

EL3044,
EL3048

Firmware 06, Rev. EL3044-000-0017
Firmware 06, Rev. EL3048-000-0017

EL3051,
EL3052

Firmware 05, Rev. EL3051-000-0017
Firmware 05, Rev. EL3052-000-0017

EL3054,
EL3058

Firmware 06, Rev. EL3054-000-0017
Firmware 06, Rev. EL3058-000-0017

EL3061,
EL3062

Firmware 04, Rev. EL3061-000-0017
Firmware 04, Rev. EL3061-000-0017

EL3064,
EL3068

Firmware 06, Rev. EL3064-000-0017
Firmware 06, Rev. EL3068-000-0017

EL3072,
EL3074

Firmware 02, Rev. EL3072-0000-0016
Firmware 02, Rev. EL3074-0000-0016

Example for EL3062:

Channel 1; Limit 1 and Limit 2 enabled, Limit 1 = 2.8 V, Limit 2 = 7.4 V, representation: signed integer

Specification of the limit values:

Output of the limit value evaluation

Input channel 1

Index 0x6000:03

Index 0x6000:05

1.8 V

0x01hex, (Limit 1, limit value undershot)

0x01hex, (Limit 2, limit value undershot)

2.8 V

0x03hex, (Limit 1, limit value reached)

0x01hex, (Limit 2, limit value undershot)

4.2 V

0x02hex, (Limit 1, limit value exceeded)

0x01hex, (Limit 2, limit value undershot)

8.5 V

0x02hex, (Limit 1, limit value exceeded)

0x02hex, (Limit 2, limit value exceeded)

Limit, Swap limit 2:

Linking in the PLC with 2-bit values

The limit information consists of 2 bits. Limitn can be linked to the PLC or a task in the System Manager.

Limit, Swap limit 4:Fig.232: Linking of 2-bit variable to additional task