EL3004 - Connection, display and diagnostics

EL3004 - Connection, display and diagnostics 1:Fig.9: LEDs and connection EL3004

EL3004 - Connection

Terminal point

Description

Internally connected
with connection

Max. current carrying capacity *)

Name

No.

Input 1

1

Input 1

-

not applicable (voltage input)

GND

2

Signal ground for input 1

4,6,8

40 mA

Input 3

3

Input 3

-

not applicable (voltage input)

GND

4

Signal ground for input 3

2,6,8

40 mA

Input 2

5

Input 2

-

not applicable (voltage input)

GND

6

Signal ground for input 2

2,4,8

40 mA

Input 4

7

Input 4

-

not applicable (voltage input)

GND

8

Signal ground for input 4

2,4,6

40 mA

*) Constant and peak value

RUN - LEDs

LED

Color

Meaning

RUN *)

green

These LEDs indicate the terminal's operating state:

off

State of the EtherCAT State Machine: INIT = initialization of the terminal or BOOTSTRAP = function for firmware updates of the terminal

flashing

State of the EtherCAT State Machine: PREOP = function for mailbox communication and different standard-settings set

single flash

State of the EtherCAT State Machine: SAFEOP = verification of the Sync Manager channels and the distributed clocks.
Outputs remain in safe state

on

State of the EtherCAT State Machine: OP = normal operating state; mailbox and process data communication is possible

*) If several RUN LEDs are present, all of them have the same function.