Installation instructions for cascaded connection

Observe the following instructions for using cascaded analog inputs!

1. All channels of a terminal must be used consecutively; gaps in usage, that is, unused terminal connection points (points 2, 3, 4, 5, 6, 7, and 8 in the connection diagram), are not recommended, as they can lead to significant measuring errors
2. The terminal is designed for the measurement of a high number of channels. The wiring between terminals must be carried out as shown in the following figure.
3. If the number of cells to be measured is less than the number of available channels (n terminals × 8), unused channels will result at the first/last terminal. Unused channels at the top/bottom end of the terminal display random values. It is therefore recommended to connect the unused channels electrically to the last used pole using wire jumpers!
4. The cascaded layout of the channels results in a channel-by-channel differential measurement; see detailed diagram: “Cell 3” has a connection to terminal connection point 3 via wire 3b and wire 3, and simultaneously has a connection to terminal connection point 4 via wire 4a and wire 4.
This means that each cell – and thus each measuring channel from the user’s perspective – is connected to 2 terminal connection points!
Therefore, when it comes to wire breaks in the system, the following distinctions must be made
Installation instructions for cascaded connection 1:
Fig.3: Cascaded measurement of 20 cells using the EL3008-000x