Technical data

Technical data

EL2878-0005

Connection technology

Flat-ribbon cable

digital outputs

8

Rated load voltage

24 VDC (-15 % / +20 %)

Load type

ohmic, inductive, lamp load

Distributed clocks

no

Max. output current

0.5 A (short-circuit proof) per channel

Short-circuit current

< 2 A typ.

Reverse polarity protection

yes

Max. breaking energy (ind.)

< 150 mJ/channel

Switching times

TON: 60 µs typ., TOFF: 300 µs typ.

Current consumption of power contacts

20 mA typ. + load from the 24 V supply (no power contacts)

Current consumption via E-bus

typ. 100 mA

Electrical isolation

500 V (E-bus/field voltage)

Special features

Diagnosis of the power supply

Bit width in process image

8 output bits, 1 diagnostic bit

Configuration

no address or configuration settings required

Conductor connection

Standard flat-ribbon cable connector (standardized according to IEC 60603-13)

2 x 10-pin connector RM 2.54 mm with locking mechanism for connecting a 2 x 10-pin connector (socket with piercing connection for flat-ribbon cables)

Weight

approx. 55 g

Permissible ambient temperature range during operation

-25 °C ... +55 °C

Permissible ambient temperature range during storage

-40 °C ... +85 °C

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 68 mm (width aligned: 12 mm)

Installation

on 35 mm mounting rail, conforms to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable

Identification / approval*)

CE, UKCA
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).