Technical data

Technical data

EL2872

EL2872-0010

digital outputs

16

Rated load voltage

24 VDC (-15 % / +20 %), max. 1 A per connection pin

Load type

ohmic, inductive, lamp load

Freedom from interference

yes (see note)

-

Max. output current

0.5 A (short-circuit proof) per channel

Short-circuit current

0.6 ... 2.0 A

Max. breaking energy (ind.)

< 150 mJ/channel

Switching times

TON: 60 µs typ., TOFF: 300 µs

TON: 50 µs typ., TOFF: 200 µs

Current consumption via E-bus

typ. 130 mA

Electrical isolation

500 V (E-bus/field voltage)

Bit width in process image

16 output bits

Configuration

no address or configuration settings required

Conductor connection

20-pin contact strip

Weight

approx. 55 g

Permissible ambient temperature range during operation

-25 °C ... +55 °C

Permissible ambient temperature range during storage

-40 °C ... +85 °C

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Installation

on 35 mm mounting rail, conforms to EN 60715

Enhanced mechanical load capacity

yes, see also Installation instructions for enhanced mechanical load capacity

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection rating

IP20

Installation position

variable

Identification / approval*)

CE, UKCA
cULus, ATEX, IECEx, CCC

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc