Technical data
Technical data | EL2808 |
|---|---|
digital outputs | 8 |
Rated load voltage | 24 VDC (-15 % / +20 %) |
Load type | ohmic, inductive, lamp load |
Max. output current | 0.5 A (short-circuit proof) per channel |
Short-circuit current | 0.6 ... 2.0 A |
Max. breaking energy (ind.) | < 150 mJ/channel |
Switching times | TON: 60 µs typ., TOFF: 300 µs typ. |
Power supply for the electronics | via the power contacts |
Current consumption via E-bus | typ. 110 mA |
Electrical isolation | 500 V (E-bus/field voltage) |
Bit width in process image | 8 output bits |
Configuration | no address or configuration settings required |
Conductor types | solid wire, stranded wire and ferrule |
Conductor connection | solid wire conductors: direct plug-in technique; stranded wire conductors and ferrules: spring actuation by screwdriver |
Rated cross-section | solid wire: 0.08 ... 1.5 mm²;stranded wire: 0.25 ... 1.5 mm²;ferrule: 0.14 … 0.75 mm² |
Weight | approx. 65 g |
Permissible ambient temperature range during operation | -25 °C ... +60 °C |
Permissible ambient temperature range during storage | -40 °C ... +85 °C |
Permissible relative air humidity | 95 %, no condensation |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) |
on 35 mm mounting rail, conforms to EN 60715 | |
Enhanced mechanical load capacity | yes, see also Installation instructions for enhanced mechanical load capacity |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection rating | IP20 |
Installation position | variable |
Identification / approval*) |
*) Real applicable approvals/markings see type plate on the side (product marking).
Ex markings
Standard | Marking |
|---|---|
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |