| Technical data | EL2869 | 
|---|---|
| Connection technology | 1-wire | 
| Digital outputs | 16 | 
| Nominal voltage | 24 VDC (-15% / +20%) | 
| Load type | ohmic, inductive, lamp load | 
| Distributed clocks | - | 
| Output current max. | 0.5 A (short-circuit proof) per channel | 
| Output stage | Push (HighSide switch) | 
| Short circuit current | < 1.5 A typ. | 
| Reverse polarity protection | yes | 
| Switch-off energy (ind.) max. | < 150 mJ/channel | 
| Switching times | TON: 60 µs typ., TOFF: 300 µs typ. | 
| Current consumption E-bus | 60 mA typ. | 
| Electrical isolation | 500 V (E-bus/field voltage) | 
| Current consumption power contacts | 50 mA typ. + load | 
| Bit width in process image | 16 bit output, 16 bit diagnostics | 
| NoCoeStorage functionality | yes | 
| Configuration | via TwinCAT System Manager | 
| Special features | Diagnosis via process data and LED: Overload (channel by channel) | 
| Weight | approx. 60 g | 
| Permissible ambient temperature range during operation | -25 °C ... +60 °C (extended temperature range) | 
| Permissible ambient temperature range during storage | -40 °C ... +85 °C | 
| Permissible relative humidity | 95%, no condensation | 
| Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width in alignment: 12 mm) | 
| on 35 mm mounting rail according to EN 60715 | |
| Vibration / shock resistance | according to EN 60068-2-6 / EN 60068-2-27 | 
| EMC resistance / emission | according to EN 61000-6-2 / EN 61000-6-4 | 
| Protection class | IP20 | 
| Mounting position | variable | 
| Marking / Approval*) | CE, UKCA,  | 
*) Real applicable approvals/markings see type plate on the side (product marking).