EL2624, EL2634 - LEDs and connection

CAUTION

Risk of injury!

Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!

Notice

Possible damage of devices!

When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 VAC and 24 VDC), please note that it is mandatory to use potential separation terminals*!

*e.g.: EL9080

CAUTION

Risk of injury and/or damage to the devices possible!

It is not permitted to assign different switching voltages (e.g. 230 VAC and 24 VDC) to the channels (switching contacts of the relays) because safety-relevant clearances and creepage distances cannot be maintained in this way!

EL2624, EL2634 - LEDs and connection 1:
EL2624, EL2634

EL2624, EL2634 - LEDs

LED

Color

Meaning

Signal 1 - 4

green

off

Terminal points 1-2 (Channel 1),  5-6 (Channel 2),
3-4 (Channel 3) resp.7-8 (Channel 4) open

on

Terminal points 1-2 (Channel 1),  5-6 (Channel 2),
3-4 (Channel 3) resp.7-8 (Channel 4) closed

EL2624, EL2634 - Connection

Terminal

Meaning

Description

No.

1 3

1

Relay 1, NO contact

1 4

2

3 3

3

Relay 3, NO contact

3 4

4

2 3

5

Relay 2, NO contact

2 4

6

4 3

7

Relay 4, NO contact

4 4

8