EL2622, EL2622-0010 - LEDs and connection

Bring the bus system into a safe, powered down state before starting installation, disassembly or wiring of the Bus Terminals!
When designing a Bus Terminal block with different potentials on the power contacts (e.g. 230 VAC and 24 VDC), please note that it is mandatory to use potential separation terminals*!
*e.g.: EL9080

EL2622, EL2622-0010 - LEDs | |||
---|---|---|---|
LED | Color | State | Meaning |
Relay 1, | green | off | Terminal points 1-2 (Channel 1) and 5-6 respectively (Channel 2) not connected |
on | Terminal points 1-2 (Channel 1) and 5-6 respectively (Channel 2) connected | ||
Status (EL2622-0010 only) | green | off | Terminal not synchronized (relay switches without delay e.g. by DC supply) |
on | Terminal is synchronized on mains frequency |
EL2622, EL2622-0010 - Connection | ||
---|---|---|
Terminal | Meaning | |
Description | No. | |
Relay 1 | 1 | Relay 1, NO contact |
.. 230 VAC /..30 VDC | 2 | ≤ 230 VAC resp. ≤ 30 VDC |
EL2622: - | 3 | EL2622: not connected |
PE | 4 | PE (internally connected with terminal point 8) |
Relay 2 | 5 | Relay 2, NO contact |
.. 230 VAC /..30 VDC | 6 | ≤ 230 VAC resp. ≤ 30 VDC |
EL2622: - | 7 | EL2622: not connected |
PE | 8 | PE (internally connected with terminal point 4) |