Technical data
Technical data | EL2595 |
|---|---|
Application recommendation | Continuous light >300 mA and simple lighting applications |
Connection technology | 2-wire |
Number of outputs | 1 |
Input voltage (power contacts) | 24 VDC (-15 %/+20 %) |
Rated load voltage | 2 - 48 VDC, (controlled automatically, observe the dead band in control mode) |
Load type | resistive |
Distributed clocks | yes |
Distr. Clocks accuracy | << 1 µs |
Min. output current (continuous) | 300 mA |
Max. output current (continuous) | 700 mA (short-circuit proof) |
Switching times | 200 µs to endless |
Trigger input | max. 24 V, typ. 8 mA max., switching level approx. 3 V, reverse polarity up to max. 5 V maximum load |
Current consumption via E-bus | typ. 110 mA |
Electrical isolation | 500 V (E-bus/field voltage) |
Current consumption power contacts | typ. 20 mA + load |
Special features | optional automatic operation in case of communication interruption, extensive real-time diagnostics, external trigger input |
Power supply for the electronics | via the E-bus |
Configuration | via TwinCAT System Manager |
Weight | approx. 55 g |
Permissible ambient temperature range during operation | 0 °C ... + 55 °C |
Permissible ambient temperature range during storage | -25 °C ... + 85 °C |
Permissible relative air humidity | 95 %, no condensation |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) |
on 35 mm mounting rail according to EN 60715 | |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP20 |
Installation position | prescribed installation position - see note! |
Approval | CE |