Technical data

Technical data

EL2595

Application recommendation

Continuous light >300 mA and simple lighting applications

Connection technology

2-wire

Number of outputs

1

Input voltage (power contacts)

24 VDC (-15 %/+20 %)

Rated load voltage

2 - 48 VDC, (controlled automatically, observe the dead band in control mode)

Load type

resistive

Distributed clocks

yes

Distr. Clocks accuracy

<< 1 µs

Min. output current (continuous)

300 mA

Max. output current (continuous)

700 mA (short-circuit proof)

Switching times

200 µs to endless

Trigger input

max. 24 V, typ. 8 mA max., switching level approx. 3 V, reverse polarity up to max. 5 V maximum load

Current consumption via E-bus

typ. 110 mA

Electrical isolation

500 V (E-bus/field voltage)

Current consumption power contacts

typ. 20 mA + load

Special features

optional automatic operation in case of communication interruption, extensive real-time diagnostics, external trigger input

Power supply for the electronics

via the E-bus

Configuration

via TwinCAT System Manager

Weight

approx. 55 g

Permissible ambient temperature range during operation

0 °C ... + 55 °C

Permissible ambient temperature range during storage

-25 °C ... + 85 °C

Permissible relative air humidity

95 %, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail according to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

prescribed installation position - see note!

Approval

CE