Connection
Before commissioning in TwinCAT, connect the terminal as follows:
- Supply the EL2574 via the power contacts with 24 VDC.
- Connect the data line (and clock line) to the appropriate terminal points.
- Connect the LED supply via the terminal or directly to the LEDs (see note from chapter "Supply of the connected LEDs"). Note here that the terminal only serves as a rail.
| Connection instructions - Make sure that the supply of the LED has the same 0 V potential as the 0 V power contact, as this is the reference ground of the terminal. The 0 V power contact is also internally connected to terminal points GND.
- Shielded cables are mandatory for connecting the LED.
- For stable data transmission, the data and supply lines for the LED should be kept as short as possible and should not be routed past switching elements.
|