Technical data
Technical data | EL2522 |
|---|---|
Digital outputs | RS422 differential outputs |
Signal voltage | RS422 level (differential: min. 1 V, max. 3 V) |
Load type | RS422 and optocoupler, min. 120 Ω |
Max. output current (per channel) | 50 mA, RS422 specification |
Output frequency | 0…4 million increments/s (equivalent to 1 MHz with 4‑fold evaluation) |
Duty cycle | 50% (±10%) |
Resolution | max. 15 bits |
Step size | min. 10 ns (internal) |
Power supply for the electronics | via the E-bus |
Current consumption via E-bus | 120 mA typ. |
Electrical isolation | 500 V (E-bus/field voltage) |
Bit width in process image | default 14 bytes Data in, 28 bytes Data out |
Configuration | via TwinCAT System Manager |
Weight | approx. 50 g |
Approved ambient temperature range during operation | -25...+60°C |
Approved ambient temperature range during storage | -40...+85°C |
Approved relative air humidity | 95%, no condensation |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm |
on 35 mm DIN mounting rail, conforms to EN 60715 | |
Enhanced mechanical load capacity | yes, see also Installation instructions for enhanced mechanical load capacity |
Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
Protection rating | IP20 |
Installation position | variable |
Approvals/markings*) | CE, EAC, UKCA |
*) Real applicable approvals/markings see type plate on the side (product marking).