Basic function

The EL2502-0005 has three basic operation modes with additional selection options per channel. These are accessed via the PDO selection.

This mode is to be used if the duty factor only is to be quickly changed in the real-time context.

Operating range

Note

CoE
0x80n0:07

Period value from

Period unit

Permissible value range

Frequency range

PWM 20 Hz ... 20 kHz

 

0

CoE 0x80n0:15

[1000 ns = 1 µs]

80 ... 32657 (signed)
80 … 65535 (unsigned)

20 Hz … 20 kHz

PWM 100 ns
frequency resolution

 

2

CoE 0x80n0:15

[100 ns]

 

153 Hz ... 125 kHz

PWM 1 Hz ... 20 kHz

 

3

CoE 0x80n0:16

[1000 ns = 1 µs]

 

1 Hz ... 20 kHz

The corresponding output frequency can be calculated from the period.
Note re. "100 ns" mode: Values < 80 [*100 ns] (equivalent to 125 kHz) cannot be processed. If such an invalid value is entered in the CoE, the terminal has to be started in PREOP state, so that the CoE entry can be corrected in this state.

This mode is to be used if the duty factor and the frequency are to be quickly changed in the real-time context.

Operating range

Note

CoE
0x80n0:07

Period value from

Period unit

Permissible value range

Frequency range

PWM 20 Hz

 

not relevant

Process data

[1000 ns = 1 µs]

0 ... 65535
(only unsigned)

20 Hz ... 20 kHz (typ. 17 ... 21 kHz)

This mode is to be used if the duty factor and the frequency are to be quickly changed in the real-time context. The frequency can be set to min. 1 Hz.

Operating range

Note

CoE
0x80n0:07

Period value from

Period unit

Permissible value range

Frequency range

PWM 1 Hz ... 20 kHz

 

not relevant

Process data

[1000 ns = 1 µs]

0 ... 1000000

1 Hz ... 20 kHz

The basic setting is made via the PDO (process data) selection in the ProcessData tab. This can be done

Basic function 1:
Example operating mode selection (EL2502)

The parameters are considered in the following order:

Basic function 2:
EL2502-0005 data flow diagram