EL2262 - Technical data
Technical data | EL2262 |
|---|---|
Digital outputs | 2 |
Rated voltage of the outputs | 24 VDC (-15%/+20%) |
Oversampling factor | n = integer multiple of the cycle time, 1...1000 |
1 Msample/s, min. period: 1 µs; (max. 100 kHz recommended up to and including hardware 05) | |
Load type | ohmic, inductive, lamp load |
Output current per channel | max. 0.5 A (short-circuit-proof in push mode) |
Current limitation | typ. 4 A / 150 µs |
Breaking energy (ind.) per channel | < 150 mJ |
Switching times Ton/Toff | < 1 µs |
Current consumption via E-bus | typ. 70 mA |
Current consumption via power voltage | typ. 35 mA + load |
Electrical isolation | 500 V (E-bus/field voltage) |
Distributed Clocks (DC) | yes |
Distributed clock (DC) precision | << 1 µs |
Bit width in process image | max. 504 bytes output, max. 4 bytes input |
Configuration | with TwinCAT System Manager |
Weight | approx. 60 g |
Permissible ambient temperature range during operation | 0°C ... + 55°C |
Permissible ambient temperature range during storage | -25°C ... + 85°C |
Permissible relative humidity | 95%, no condensation |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) |
on 35 mm mounting rail conforms to EN 60715 | |
Enhanced mechanical load capacity | yes, see also installation instructions for terminals with increased mechanical load capacity |
Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP20 |
Installation position | variable |
Marking / Approval*) |
*) Real applicable approvals/markings see type plate on the side (product marking).
Ex markings
Standard | Marking |
|---|---|
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |