Interference-free Bus Terminals

Interference-free Bus Terminals 1:

Use of interference-free Bus or EtherCAT Terminals in safety applications

If a Bus or EtherCAT Terminal is described as interference-free, this means that the consecutive terminal behaves passively in a safety application (e.g. in the case of the all-pole switch-off of a potential group).
In this case the terminals do not represent an active part of the safety controller and do not affect the Safety Integrity Level (SIL) or Performance Level (PL) attained in the safety application.
For details, please refer chapter “All-pole disconnection of a potential group with downstream interference-free standard terminals (Category 4, PL e)” and following in the TwinSAFE application manual.

Notice

Pay attention to the hardware version

Please pay attention to the information about the hardware version and non-reactivity of the respective Bus Terminal in the chapters "Technical Data" or "Firmware Compatibility"!
Only terminals with the appropriate hardware version may be used without the attained SIL/PL being affected!

The Bus or EtherCAT Terminals regarded as interference-free at the time of preparing this document are listed in the following tables together with their respective hardware versions.

Terminal name
Bus Terminal

from hardware version

KL2408

05

KL2809

02

KL2134

09

KL2424

05

KL9110

07

Terminal name
EL/ELX terminal

from hardware version

EL2004

15

EL2008

07

EL2014

00

EL2022

09

EL2024

06

EL2034

06

EL2044

01

EL2068

00

EL2212

00

EL2809

01

EL2819

00

EL2828

00

EL2869

00

EL2872

01

EL2878-0005

00

EL9110

13

EL9184

00

EL9185

00

EL9186

00

EL9187

00

EL9410

16

ELX1052

00

ELX1054

00

ELX1058

00

ELX2002

00

ELX2008

00

ELX3152

00

ELX3181

00

ELX3202

00

ELX3204

00

ELX3252

00

ELX3312

00

ELX3314

00

ELX3351

00

ELX4181

00

ELX5151

00

ELX9560

03

External wiring

The following requirements are to be ensured by the system manufacturer and must be incorporated into the user documentation.

Summary of safety classifications

Feedback avoidance measures

DIN EN ISO 13849-1

IEC 61508

EN 62061

Fault exclusion

Cable short-circuit

max.

Cat. 4

PLe

max. SIL3

max. SIL2 *

Ground feedback and all-pole disconnection

max. SIL3

Note: All terminals in a potential group must be interference-free and it must be ensured that no energy is fed back by external circuitry, even in the event of a fault.