Distributed Clocks input/output data
Index 0xF600 DC Inputs
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default | ||
---|---|---|---|---|---|---|---|
F600:0 |
DC Inputs |
|
UINT8 |
RO |
0x01 (1dec) | ||
F600:01 |
Feedback |
read-back output values |
Bit 0 |
Output channel 1 (Index 6000:02) |
UINT8 |
RO |
0x00 (0dec) |
Bit 1 |
Tristate channel 1 (Index 6000:03) | ||||||
Bit 2 |
Output channel 2 (Index 6010:02) | ||||||
Bit 3 |
Tristate channel 2 (Index 6010:03) |
Index 0xF700 DC Outputs
Index (hex) |
Name |
Meaning |
Data type |
Flags |
Default |
---|---|---|---|---|---|
F700:0 |
DC Outputs |
|
UINT8 |
RO |
0x03 (3dec) |
F700:01 |
Activate |
This byte activates a new start time in the terminal through the transition 0 → 3 |
UINT8 |
RO |
0x00 (0dec) |
F700:03 |
Start time |
Value of the next desired switching event |
UINT64 |
RO |
|