EL2014 - Technical data

Technical data

EL2014

Connection technology

1-wire

digital outputs

4

Rated load voltage

24 VDC (-15% / +20%)

Load type

ohmic, inductive, lamp load

Distributed clocks

No

Max. output current

0.5 A (short-circuit-proof) per channel

Short circuit current

< 1 A typ.

Switch-off energy (inductive)

< 150 mJ/channel

Output stage

push (high-side switch)

Reverse voltage protection

Yes

Switching times

TON: 50 µs typ., TOFF: 100 µs typ.

Supply voltage for electronic

Via the power contacts

Current consumption via E-bus

typ. 60 mA

Recommended cycle time

≥ 200 µs; with cycle times < 200 µs the process data is not updated in each cycle.

Current consumption of power contacts

typ. 15 mA + load

Electrical isolation

500 V (E-bus/field voltage)

Bit width in process image

4-bit output and 20-bit diagnostics

Supports NoCoeStorage function

Yes

Configuration

via System Manager

Conductor types

solid wire, stranded wire and ferrule

Special features

diagnostics via process data and LED: overtemperature, PowerFail, short circuit (per channel)

Weight

approx. 70 g

Permissible ambient temperature range during operation

-25 °C ... +60°C

Permissible ambient temperature range during storage

-40 °C ... +85 °C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, UKCA, EAC, CCC
ATEX, IECEx, cFMus,

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc

cFMus

Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc