EL2014 - LEDs and pin assignment
 Fig.12: EL2014
Fig.12: EL2014EL2014 - LEDs
| LED | Color | Meaning | |
|---|---|---|---|
| OUTPUT 1- 4 | green | off | No output signal | 
| on | Output signal 24 V | ||
| OUTPUT 1- 4 | red | on | ERROR: Overcurrent / Overtemperature | 
| 
 | Flashing red | ERROR: Short circuit to 24V | |
| OUTPUT 1- 4 | red / green alternating | ERROR: Open Load | |
EL2014 - Pin assignment
| Terminal point | Description | |
|---|---|---|
| Designation | No. | |
| Output 1 | 1 | Output 1 | 
| 0 V | 2 | Ground for output 1 (internally connected to terminal point 3, 6, 7 and negative power contact) | 
| 0 V | 3 | Ground for output 3 (internally connected to terminal point 2, 6, 7 and negative power contact) | 
| Output 3 | 4 | Output 3 | 
| Output 2 | 5 | Output 2 | 
| 0 V | 6 | Ground for output 2 (internally connected to terminal point 2, 3, 7 and negative power contact) | 
| 0 V | 7 | Ground for output 4 (internally connected to terminal point 2, 3, 6 and negative power contact) | 
| Output 4 | 8 | Output 4 |