EL2084 - LEDs and connection

EL2084 - LEDs and connection 1:Fig.33: EL2084

EL2084 - LEDs

LED

Color

Meaning

OUTPUT 1- 4

green

off

No output signal is present at the respective output

on

A 0 V output signal is present at the respective output

EL2084 - Connection

Terminal point

Description

Name

No.

Output 1

1

Output 1 (0 V)

24 V

2

+24 V for output 1 (internally connected to terminal points 3, 6, 7 and positive power contact)

24 V

3

+24 V for output 3 (internally connected to terminal points 2, 6, 7 and positive power contact)

Output 3

4

Output 3 (0 V)

Output 2

5

Output 2 (0 V)

24 V

6

+24 V for output 2 (internally connected to terminal points 2, 3, 7 and positive power contact)

24 V

7

+24 V for output 4 (internally connected to terminal points 2, 3, 6 and positive power contact)

Output 4

8

Output 4 (0 V)