EL2032 - LEDs and connection
Fig.28: EL2032EL2032 - LEDs
|
LED |
Color |
Meaning | |
|---|---|---|---|
|
OUTPUT 1 |
green |
off |
No output signal is present. |
|
on |
A 24 VDC output signal is present. | ||
|
ERROR 1 |
red |
Fault indication in the event of interruption or overload of the output voltage | |
EL2032 - Connection
Terminal point | Description | |
|---|---|---|
Name | No. | |
Output 1 | 1 | Output 1 |
+24 V | 2 | +24 V (internally connected to terminal point 6 and positive power contact) |
0 V | 3 | Ground for output 1 (internally connected to terminal point 7 and negative power contact) |
⏚ | 4 | ⏚ contact (internally connected to terminal point 8 and ⏚ power contact) |
Output 2 | 5 | Output 2 |
+24 V | 6 | +24 V (internally connected to terminal point 2 and positive power contact) |
0 V | 7 | Ground for output 2 (internally connected to terminal point 3 and negative power contact) |
⏚ | 8 | ⏚ contact (internally connected to terminal point 4 and ⏚ power contact) |