EL2032, EL2034 - Technical data
Technical data | EL2032 | EL2034 |
|---|---|---|
Number of outputs | 2 | 4 |
Reverse voltage protection | yes | |
Load type | ohmic, inductive, lamp load | |
Rated voltage of the outputs | 24 VDC (-15% / +20%) | |
Switching times | TON: 40 µs typ.; TOFF: 200 µs typ. | |
Output current max. per channel | max. 2 A (short-circuit-proof) | |
Short circuit and open circuit detection | yes; open circuit detection from approx. 1 A regular output current | |
Switch-off energy (inductive) | < 1.7 J/channel | |
Current consumption from load voltage | typ. 12 mA + load | typ. 14 mA + load |
Supply voltage for electronic | via E-Bus | |
Current consumption via E-bus | typ. 100 mA | typ. 120 mA |
Electrical isolation | 500 V (E-bus/field voltage) | |
Bit width in the process image | 2 output bits, 2 input bits (diagnostic) | 4 output bits, 4 input bits (diagnostic) |
Configuration | no address setting, configuration via TwinCAT System Manager | |
Weight | approx. 55 g | |
Permissible ambient temperature range during operation | -25°C ... +60°C | |
Permissible ambient temperature range during storage | -40°C ... +85°C | |
Permissible relative humidity | 95%, no condensation | |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) | |
on 35 mm mounting rail conforms to EN 60715 | ||
Vibration/shock resistance | according to EN 60068-2-6/EN 60068-2-27, | |
EMC resistance burst/ESD | conforms to EN 61000-6-2 / EN 61000-6-4 | |
Protection class | IP20 | |
Installation position | variable | |
Marking / Approval*) | ||
*) Real applicable approvals/markings see type plate on the side (product marking).
Ex markings
Standard | Marking |
|---|---|
ATEX | II 3 G Ex ec IIC T4 Gc |
IECEx | Ex ec IIC T4 Gc |