EL2022, EL2024, EL2024-0010 - Technical data

Technical data

EL2022

EL2024

EL2024-0010

Number of outputs

2

4

Non-reactive outputs

-

yes
(see notice)

-

Reverse voltage protection

yes

Load type

ohmic, inductive, lamp load

Nominal output voltage

24 VDC (-15% / +20%)

12 VDC (-15% / +20%)

Switching times

TON: 40 µs typ.; TOFF: 200 µs typ.

Output current max. per channel

max. 2 A (short-circuit-proof)

Switch-off energy (inductive)

< 1.7 J/channel

Current consumption from load voltage

typ. 9 mA + load

typ. 13 mA + load

Supply voltage for electronic

via the E-Bus

Current consumption via E-bus

typ. 100 mA

typ. 120 mA

Electrical isolation

500 V (E-bus/field voltage)

Bit width in the process image

2 output bits

4 output bits

Configuration

no address setting, configuration via TwinCAT System Manager

Weight

approx. 55 g

Permissible ambient temperature range during operation

-25°C ... +60°C

0°C ... + 55°C

Permissible ambient temperature range during storage

-40°C ... +85°C

-25°C ... + 85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Vibration/shock resistance

according to EN 60068-2-6/EN 60068-2-27,
see also Installation instructions for terminals with increased mechanical load capacity

EMC resistance burst/ESD

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, UKCA, EAC, CCC
cULus, ATEX, IECEx, cFMus

CE, UKCA, EAC, CCC
cULus, ATEX, IECEx

CE, UKCA, EAC, CCC
cULus, ATEX, IECEx

*) Real applicable approvals/markings see type plate on the side (product marking).

Ex markings

Standard

Marking

ATEX

II 3 G Ex ec IIC T4 Gc

IECEx

Ex ec IIC T4 Gc

cFMus

Class I, Division 2, Groups A, B, C, D
Class I, Zone 2, AEx/Ex ec IIC T4 Gc