Technical data
Technical data | EL2044 |
|---|---|
Connection technology | 2-wire |
Number of outputs | 4 |
Nominal voltage | 24 VDC (-15% / +20%) |
Load type | ohmic, inductive, lamp load up to 24 W max. |
Max. output current | 2 A (short-circuit proof) per channel, with diagnostics |
Output stage | push (high-side switch) |
Short circuit current | < 4 A typ. |
Reverse polarity protection | yes |
Switching times | TON: 50 µs typ., TOFF: 100 µs typ. |
Power supply for the electronics | via the power contacts |
Breaking energy | < 150 mJ/channel typ. |
Current consumption via E-bus | typ. 55 mA |
Recommended cycle time | ≥ 200 µs; |
Electrical isolation | 500 V (E-bus/field voltage) |
Current consumption power contacts | typ. 25 mA + load |
Supports NoCoeStorage function | yes |
Configuration | via System Manager |
Conductor types | solid wire, stranded wire and ferrule |
Special features | diagnostics via process data and LED: overtemperature, PowerFail, short circuit (per channel), open load detection |
Weight | approx. 50 g |
Permissible ambient temperature range during operation | 0 °C ... +55 °C |
Permissible ambient temperature range during storage | -25 °C ... +85 °C |
Permissible relative air humidity | 95%, no condensation |
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) |
Mounting | on 35 mm mounting rail according to EN 60715 |
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27, |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP20 |
Installation position | variable |
Marking | CE, UKCA, EAC |