Technical data

Technical data

EL1702-0020

Connection technology

Four-wire

Digital inputs

2

Nominal voltage of the inputs

220 V DC

Signal voltage "0"

0…100 V

Signal voltage "1"

180…264 V

Input current

typ. 1.4 mA

Input filter

3 ms typ.

Distributed Clocks

-

Current consumption Power contacts

load-dependent

Current consumption via E-bus

55 mA txp.

Electrical isolation

500 V (E-bus/field voltage)

Configuration

no address or configuration settings required

Weight

approx. 60 g

Permissible ambient temperature range during operation

0…+55 °C

Permissible ambient temperature range during storage

-25 °C ... +85 °C

Permissible relative air humidity

95 %, no condensation

Operating height

max. 2000 m

Overvoltage category

II (see also UL note)

Degree of pollution

2

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting and wiring

on 35 mm support rail according to EN 60715

Vibration / shock resistance

conforms to EN 60068-2-6/EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approvals*)

CE, EAC, UKCA
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).