Technical data
Technical data | EL1429 |
|---|---|
Connection technology | 1-wire |
Specification | positive/ground switching |
Number of inputs | 16 |
Nominal voltage | 24 VDC (-15 %/+20 %) |
Signal voltage "0" | 9…15 VDC at 24 V nominal voltage |
Signal voltage "1" | 0...5 VDC and 19...24 VDC at 24 VDC nominal voltage |
Input filter | 3 ms typ. |
Input current | 2.5 mA typ. (at 24 VDC) |
Current consumption via E-bus | 110 mA typ. |
Current consumption of power contacts | 2 mA typ. + load |
Distributed clocks | - |
Electrical isolation | 500 V (E-bus/field voltage) |
Weight | approx. 65 g |
Permissible ambient temperature range during operation | -25…+60°C (extended temperature range) |
Permissible ambient temperature range during storage | -40…+85 °C |
Permissible relative air humidity | 95%, no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection rating | IP20 |
Installation position | variable |
Pluggable wiring | no |
Approvals/markings*) | CE, cULus |
*) Real applicable approvals/markings see type plate on the side (product marking).