Technical data

Technical data

EL1382

Digital inputs

2

Specification

Thermistor PTC

Connection technology

2-wire

Rated voltage

24 VDC (-15%/+20%)

Signal voltage “0”

≤ 1.5 kΩ

Signal voltage “1”

≥ 3 kΩ

Sensor voltage

≤ 5 V

Diagnostics

open-circuit monitoring > 12 kΩ, short-circuit diagnostic < 25 Ω

Width in the process image

2 x Input, 2 x Error

Input filter

30 ms

Current consumption of power contacts

-

Supply voltage for electronics

via the E-bus

Current consumption via E-bus

typ. 120 mA

Electrical isolation

500 V (E-bus/field voltage)

Configuration

no address or configuration settings required

Weight

approx. 55 g

Permissible ambient temperature range during operation

-25°C ... +60°C

Permissible ambient temperature range during storage

-40°C ... +85°C

Permissible relative humidity

95%, no condensation

Dimensions (W x H x D)

approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)

Mounting

on 35 mm mounting rail conforms to EN 60715

Terminal with increased mechanical load capacity

yes, see also installation instructions for terminals with increased mechanical load capacity

Vibration/shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP20

Installation position

variable

Marking / Approval*)

CE, EAC, UKCA
cULus

*) Real applicable approvals/markings see type plate on the side (product marking).