Technical data
Technical data | EL1262 | EL1264 | EL1262‑0050 | |||
|---|---|---|---|---|---|---|
Digital inputs | 2 | 4 | 2 | |||
Nominal voltage of the inputs | 24 VDC (-15 %/+20 %) | 5 VDC (-15 %/+20 %) | ||||
Signal voltage "0" | -3 V … +5 V (based on EN 61131-2, type 3) | < 0.8 V | ||||
Signal voltage "1" | +11 V … +30 V (based on EN 61131-2, type 3) | >2.4 V | ||||
Input current | typ. 3 mA (based on EN 61131-2, type 3) | typ. 50 µA | ||||
Input filter delay | < 1 µs typ. | |||||
Oversampling factor | n = integer multiple of the cycle time, 1...1000 | |||||
Accuracy Distributed Clocks (DC) | << 1 µs | |||||
Sampling rate | max. 1 Msamples/s | |||||
Power supply for the electronics | via the power contacts (24 V) | via the power contacts (5 V) | ||||
Current consumption via E-bus | typ. 70 mA | typ. 80 mA | typ. 70 mA | |||
Electrical isolation | 500 V (E-bus/field potential) | |||||
Bit width in process image | n x 2 Inputs + 64-Bit-CycleCounter/Latch | 4 x (n Inputs + 2 Byte CycleCounter) | n x 2 Inputs + 64-Bit-CycleCounter/Latch | |||
Configuration | via TwinCAT System Manager | |||||
Weight | approx. 55 g | |||||
Permissible ambient temperature range during operation | 0 °C ... + 55 °C | |||||
Permissible ambient temperature range during storage | -25 °C ... + 85 °C | |||||
Permissible relative air humidity | 95 %, no condensation | |||||
Dimensions (W x H x D) | approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm) | |||||
on 35 mm mounting rail, conforms to EN 60715 | ||||||
Vibration / shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 | |||||
EMC immunity / emission | in accordance with EN 61000-6-2 / EN 61000-6-4 | |||||
Protection rating | IP20 | |||||
Installation position | variable | |||||
Approvals *) | CE, EAC, UKCA | |||||
*) Real applicable approvals/markings see type plate on the side (product marking).
Ex markings
Standard | Marking |
|---|---|
ATEX | II 3 G Ex nA IIC T4 Gc |
IECEx | Ex nA IIC T4 Gc |
cFMus | Class I, Division 2, Groups A, B, C, D |
![]() | Electrical supply The fast input circuits of the EL1262/EL1264 are supplied via the power contacts. Please note that the EL1262-0050 can only be operated with a 5 V supply voltage! If necessary, use a EL9505 power supply terminal for supplying the EL1262-0050. |