EL1262-xxxx - LEDs and pin assignment

EL1262-0000

EL1262-xxxx - LEDs and pin assignment 1:
EL1262-0000

EL1262-0000 pin assignment

Terminal point

Description

Name

No.

Input 1

1

Input 1

+ 24 V

2

+24 V (internally connected to terminal point 6 and positive power contact)

0 V

3

0 V (internally connected to terminal point 7 and negative power contact)

PE

4

PE contact

Input 2

5

Input 2

+ 24 V

6

+24 V (internally connected to terminal point 2 and positive power contact)

0 V

7

0 V (internally connected to terminal point 3 and negative power contact)

PE

8

PE contact

LEDs

LED

Color

Meaning

INPUT 1

INPUT 2

green

off

There is no input signal at the respective input

on

+24 V input signal at the respective input

EL1262-0050

EL1262-xxxx - LEDs and pin assignment 2:
EL1262-0050
Note
Be sure the correct supply voltage is used!

The EL1262-0050 can only be operated with a 5 V supply voltage! The terminal will not work in a terminal network with a 24 V supply voltage at the power contacts! If necessary, use a EL9505 power supply terminal for supplying the EL1262-0050.

EL1262-0050 pin assignment

Terminal point

Description

Name

No.

Input 1

1

Input 1

+ 5 V

2

+5 V (internally connected to terminal point 6 and positive power contact)

0 V

3

0 V (internally connected to terminal point 7 and negative power contact)

PE

4

PE contact

Input 2

5

Input 2

+ 5 V

6

+ 5 V (internally connected to terminal point 2 and positive power contact)

0 V

7

0 V (internally connected to terminal point 3 and negative power contact)

PE

8

PE contact

LEDs

LED

Color

Meaning

INPUT 1

INPUT 2

green

off

There is no input signal at the respective input

on

+5 V input signal at the respective input