Commissioning in compatibility mode EL2252
The multi-timestamp terminals can also be operated in compatibility mode with regard to the EL2252. The following settings are required:
Procedure:
- The changeover should only be implemented via the predefined PDO:
Fig.179: Predefined PDOs for compatibility mode- CoE 0x70n0:0 MTO outputs Ch.n (n=8...F) can be used for configuration, similar to the EL2252. In addition the EL2252 offers a tristate PDO for high-resistance switching of the channels. This PDO is not available for the EL2258.
|
0x70n0:0 MTO Output Ch. n=8...F |
Name |
Entry |
Description |
|---|---|---|---|
|
70n1:01 |
Output |
|
Activates output 0 V/24 V of channel n=1..8 |
|
0x70n0:01 FALSE |
|
0 V present at the output | |
|
0x70n0:01 TRUE |
|
24 V present at the output | |
|
70n1:11 |
Activate |
|
This byte activates a new start time in the terminal through the transition 0 --> 3 |
|
70n0:41 |
Start Time |
|
64-bit value of the next desired switching event |
![]() | Free PDO selection No provision is made for free arrangement of the respective PDOs in compatibility mode. |