Commissioning in compatibility mode

The multi-timestamp terminals can also be operated in compatibility mode with regard to the EL1252. The following settings are required:

Procedure:
  - The changeover should only be implemented via the predefined PDO:

Commissioning in compatibility mode 1:
Predefined PDOs for compatibility mode

  - Via the CoE 0x80n0:0 TSI Settings (n = 8 ... F) the response for several events in a single cycle can be specified here. This is comparable to the EL1252. In this case MTSF =1.

0x80n0:0 TSI Settings Ch. n=8...F

Name

Entry

Description

80n0:01

Pos Sample Mode

 

Defines the behavior for rising edges with several signals per cycle

80n0:01 FALSE

Last edge

The last detected event is forwarded to the PLC

80n0:01 TRUE

First edge

The first detected event is forwarded to the PLC

80n0:02

Neg Sample Mode

 

Defines the behavior for falling edges with several signals per cycle

80n0:02 FALSE

Last edge

The last detected event is forwarded to the PLC

80n0:02 TRUE

First edge

The first detected event is forwarded to the PLC

Commissioning in compatibility mode 2:

Free PDO selection

No provision is made for free arrangement of the respective PDOs in compatibility mode.