EtherNet/IP™ Configuration
EtherNet/IP™ Slave:
Fig.22: Configuration via HTML pages – EtherNet/IP™ configurationEtherNet/IP™ Device (Slave) - Device Info
All Parameters are “read only” and are for diagnostic purposes
EtherNet/IP™ Adapter (Slave) – Settings
• Error Confirmation Mode
Select User Confirmation or Automatic Confirmation. Default Setting: User Confirmation
• Ebus Fallback mode
How the Coupler responds to a break in EtherCAT.
Set to Zero, Freeze, Stop Ebus. Default Setting: Set to Zero
• FBus Fallback Mode
How the Coupler responds to a break in the FBus.
Set to Zero, Freeze, Stop Ebus. Default Setting: Set to Zero
• TCP Timeout
Maximum time allowed for Ethernet Connection. Default Setting 30 Seconds
• Unicast TTL (Time To Live)
Used to determine if an EtherNet/IP™ Frame has been in the network too long and should be discarded
Default Setting 128 Seconds
• Unicast UDP Checksum
Enable/Disable UDP Checksum – Unicast (Frames sent to Single Destination). Checksum is a digit representing the sum of the transmitted data used for error checking.
• Multicast TTL (Time to Live)
Used to determine if an EtherNet/IP™ Frame has been in the network too long and should be discarded
Default Setting 1 Second
• Multicast UDP Checksum
Enable/Disable UDP Checksum – Multicast (Copies of Frames sent to Multiple Destinations). Checksum is a digit representing the sum of the transmitted data used for error checking.
Ethernet Statistics
Fig.23: EtherNet StatisticsEthernet Rx Frames: Received Frames
Ethernet Tx Frames: Transmitted Frames
IP Stack Statistics
Fig.24: IP Stack StatisticsIp Frames: A chunk of data sent over a data link
Arp Request: A request by the host wishing to obtain a physical address on a TCP/IP Network
Arp Reply: A unicast response to a broadcast request
Echo Request: Packets sent to a target host waiting for a reply
Echo Reply: Packets sent from a target host stating that it received the echo request
Link Status Changed: Indicates the number of times the state of the physical link has changed
Frame Alloc Fails: Indicates the number of Frame Allocation Fails
Arp Timeout Frames: The number of frames that were sent and not received back in time
Dropped Frames: Indicates the number of dropped frames
Electronic Data Sheet
Create EDS File: Create an Electronic Data Sheet for Use with an EIP Master
Create L5X File: Create UDTs for Input and Output Data (For use with RSLogix 5000 Import Only)
Fig.25: Pulldown menu "Create generic description (valid for all configurations")