Technical data
Technical data | EK9500 |
---|---|
Protocol | EtherNet/IP |
Interfaces | 2 x Ethernet 100 Mbit/s, 1 x USB device (behind the front flap) |
Bus interface | 2 x RJ 45 (switched) |
I/O connection | E-Bus (EtherCAT terminals) |
Web-based Management | yes |
I/O terminals | E-bus (EL, ES, EP), standard digital signals, standard analog signals No gateway EC terminals, no EC terminals with XFC or DC function, no general EtherCAT devices |
Number of EC terminals | max. 255 |
Max. size of process data | 496 bytes input and 496 bytes output data 1) |
Supply voltage | 24 VDC (-15%/+20%) |
Power supply I/O terminals | 2 A |
Max. power loss | 3 W |
Power contacts | 24 VDC max./10 A max. |
Electrical isolation | 500 V (power contact/supply voltage/Ethernet) |
Dimensions (W x H x L) | 64 mm x 100 mm x 80 mm |
Operating/storage temperature | -25°C … +60°C/-40°C … +85°C |
Operating/storage temperature other mounting position | 0…+55 °C/-25…+85 °C |
Relative humidity | 95 % no condensation |
Vibration/shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity/emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protect. class / installation pos. | IP20/any |
Marking / Approvals*) |
*) Real applicable approvals/markings see type plate on the side (product marking).
1) The acyclic communication via GetAttributeSingle/SetAttributeSingle can be used to read and write > 1000 bytes.
Ex marking
Standard | Marking |
---|---|
ATEX | II 3 G Ex nA IIC T4 Gc |
E-Bus current/mounting positions *) - for -25°C..+60°C only horizontal mounting position, E-bus current 1 A max. |
System data | Ethernet/IP (EK9500) |
---|---|
Number of I/O modules | depending on controller |
Number of I/O points | depending on controller |
Transmission medium | 4 x 2 twisted pair copper cable category 5 (100 Mbit/s) |
Cable length | 100 m |
Data transfer rate | 100 Mbit/s |
Topology | Star-form cabling, line topology |