Meaning of the DIP switch
10-pole DIP switch S001
The DIP switch has the following meaning for the Ethernet interfaces X001 and X002, which are switched:
Fig.14: DIP switch S001: Left off ”0“, right on “1”|
DIP 9 |
DIP 10 |
Description DIP 1..8 |
Restart behavior |
Behavior with factory settings |
|---|---|---|---|---|
|
0 |
0 |
Last byte of the IP address via DIP switches 1 to 8 |
|
|
|
0 |
1 |
DHCP |
|
|
|
DHCP |
|
| ||
|
1 |
0 |
Reserved |
|
|
|
1 |
1 |
PROFINET-compliant |
|
|
|
PROFINET with fixed name |
|
|
2-pole DIP switch (under the flap between the battery and the SD card slot)
|
DIP switch (red) |
Meaning |
|---|---|
|
1 off and 2 off |
normal mode, coupler is started |
|
1 on and 2 off |
The EK starts in Config Mode; the internal Flash memory can be accessed via the USB interface (for example for an image update). |
|
1 off and 2 on |
Manufacturer's setting |
|
1 on and 2 on |
No function so far |